LNG/L-CNG – The Storage Tanks
LNG Storage Tanks
In General
- Model: vacuum insulated, horizontal assembly
- D Code: EN13458-2
- Medium: LNG
- Directive: 2014/68/EU European Approval
Inner Tank
- Filling capacity: %95 @ MAWP
- MAWP: 12 barg (maximum pressure)
- Temperature range: -196°C / +49°C
- Material: SS 1,4306 & 1,4307 or similar
- X-ray inspection: 100%
- CE label
Outer tank
- Design pressure: 1 barg
- Ambient temperature: -40°C / +50°C
- Material: Carbon Steel P355NL1 or equivalent
- Isolation: Perlite + vacuum insulation
- Perlite density: 90-100 kg/m^3